Psychrometric Mixed Air & Coil Sensible Heat Ratio (SHR)
Calculates mixed air dry-bulb temperature and humidity ratio, total AHU cooling coil capacity (kW & TR), sensible-to-total heat ratio (SHR), and moisture condensate drainage per ASHRAE Handbook of Fundamentals.
Governing Engineering Standards & Calculation Model
Governing Standards & References
- ASHRAE Handbook of Fundamentals: Chapter 1 (Psychrometrics and Moist Air Thermodynamic Properties).
- ASHRAE Standard 62.1: Ventilation for Acceptable Indoor Air Quality.
- AHRI Standard 410: Forced-Circulation Air-Cooling and Air-Heating Coils.
Engineering Equations & Derivations
W_mix = (W_ra × (1 - FA%)) + (W_oa × FA%) [kg_w / kg_da]
m_dot_da = CFM × 0.0004719 × 1.204 [kg/s]
Q_total = m_dot_da × (h_mix - h_off) [kW]
SHR = (m_dot_da × 1.006 × (T_mix - T_off)) / Q_total
Condensate = m_dot_da × (W_mix - W_off) × 3600 [L/h]
Standard saturation vapor pressures computed via Magnus-Tetens approximation. Off-coil air assumed at 95% relative humidity for typical wet-coil cooling and dehumidification regimes.
Psychrometric calculations provide preliminary thermodynamic screening and coil sizing. Actual coil performance depends on coil bypass factor (BF typically 0.05 to 0.15 for 4-row / 6-row / 8-row chilled water or DX coils), fin spacing (FPI), water entering/leaving temperatures (typically 7°C/12°C), and internal tube turbulence. Manufacturer certified coil selection software (e.g. Carrier, Trane, Dunham-Bush) must verify selection prior to coil fabrication.