Industrial Motor Starter & Protection Sizing Calculator
Calculates motor full load current (FLA), coordinates AC-3 contactor duty ratings (Main, Delta, Star), sets thermal overload relay calibration bands, and estimates backup MCCB / MPCB ratings for 3-phase induction motor feeders per IS/IEC 60947-4-1.
Governing Engineering Standards & Calculation Model
Governing Standards & References
- IS/IEC 60947-4-1: Low-voltage switchgear and controlgear — Contactors and motor-starters.
- IS 12615: 2018: Line operated three-phase induction motors — Efficiency classes (IE code).
- IS/IEC 60947-2: Low-voltage switchgear and controlgear — Circuit-breakers (MCCBs).
Engineering Equations & Derivations
Star-Delta Main & Delta Contactor = I_FLA / √3 ≈ 0.58 × I_FLA
Star-Delta Star Contactor = I_FLA / 3 ≈ 0.33 × I_FLA
DOL Main Contactor = 1.0 × I_FLA (AC-3 Duty)
Overload Relay Range = 0.85 to 1.15 × Contactor Current
Backup MCCB/MPCB sizing: Screened at $1.5\times I_{\text{FLA}}$ for Star-Delta and $2.0\times I_{\text{FLA}}$ for DOL to prevent nuisance tripping during inrush starting currents.
Contactor ratings and suggested MCCB amperages provide preliminary component sizing. Per IS/IEC 60947-4-1, complete feeder assemblies require Type 2 Coordination verification (where no damage or welding to contactors/relays occurs during short-circuit faults) based on manufacturer certified coordination tables (e.g. Schneider, ABB, L&T, Siemens). High-inertia loads (pumps, blowers, heavy crushers) require extended thermal trip class 20/30 overload relays and derated starting cycle checks.