Portal Home > Electrical > Indoor Lighting & Lux Level
Tool 13: Illumination & Lighting Engineering

Indoor Lighting Illumination Lux & Lumen Method Calculator

Applies the standard zonal cavity lumen method per IS 3646 and NBC 2016. Computes room cavity ratio (RCR), dynamic coefficient of utilization (UF), luminaire count, maintained working plane Lux, and Lighting Power Density (LPD) with ECBC compliance benchmarking.

✔ 1. Formula Verified → ⚡ 2. Engineering Screening → 📐 3. Standards Referenced (IS 3646 / ECBC 2017) → ⚖ 4. Engineer Review Required
⚙ Room Geometry & Photometric Parameters
Meters
Interior length of the conditioned space.
Meters
Interior width of the conditioned space.
Meters
Distance from fixture to working desk plane (e.g. Ceiling Height 3.5m - 0.85m desk = 2.65m).
Lux
Design target per IS 3646: 150 Lux (Warehouse), 300 Lux (Corridors), 400 Lux (Office/General), 500 Lux (Cleanroom/Inspection).
Lumens
Total rated initial lumen output per fixture (e.g. 4,800 lm for standard 40W 2x2 LED panel).
Watts
Total electrical load per luminaire including LED driver losses.
Ratio
Accounts for lamp lumen depreciation (LLD) and luminaire dirt depreciation (LDD) (typically 0.80 for clean indoor spaces).
📊 Lighting Sizing Sheet
Preliminary Screening
Required Luminaires (Lumen Method)
49 Fixtures
Maintained Illuminance: 399 Lux on Working Plane (Target: 400 Lux)
Room Area
300.0 m²
Room Cavity Ratio (RCR)
1.55 (UF: 0.64)
Connected Lighting Load
1.96 kW
Lighting Power Density
6.53 W/m²
ECBC 2017 Space Compliance
Compliant for Commercial Office (LPD ≤ 7.5 W/m²)
💬 Consult Lighting Design Team on WhatsApp

Governing Engineering Standards & Space Benchmark Allowances

Governing Standards & Formulas

  • IS 3646 (Parts 1 & 2): Code of practice for interior illumination.
  • NBC 2016 Part 8 Section 1: Building Services — Lighting and Natural Ventilation.
  • ECBC 2017: Energy Conservation Building Code (Building Area & Space-by-Space LPD limits).
RCR = 5 × H_m × (L + W) / (L × W)
N_fixtures = ⌈(E_target × Area) / (Lumens × UF × MF)⌉
Actual_Lux = (N_fixtures × Lumens × UF × MF) / Area
LPD = (N_fixtures × W_fixture) / Area [W/m²]

ECBC 2017 & NBC Illuminance / LPD Reference Table

Space Category Recommended Lux ECBC Max LPD
Commercial Office / IT 300 – 500 Lux 7.5 W/m²
Pharma / Cleanroom Assembly 400 – 600 Lux 9.5 W/m²
Industrial Workshop / Fabrication 300 – 500 Lux 8.0 W/m²
Storage / Warehouse Aisles 150 – 200 Lux 4.5 W/m²
⚖ Statutory Notice & Engineering Disclaimer (Tier D Integration)

The Lumen (Zonal Cavity) method provides average horizontal illuminance on the working plane. It assumes uniform room geometry, standard surface reflectances (80% ceiling, 50% walls, 20% floor), and symmetrical fixture layout. It does not account for point-to-point uniformity ratios ($U_0 \ge 0.60$), unified glare rating (UGR ≤ 19), or task shading. High-precision architectural lighting layouts require point-by-point DIALux or AGi32 photometric simulation prior to fixture procurement.